CAT6 flat vs round CAT6 in a lift shaft

Installers put round CAT6 in lift shafts every week. Here is what fails, when, and what to use instead.

Round CAT6 is the cable everyone has on the van, so it is the cable that goes into the shaft when a lift camera is added in a hurry. It works on the day. The problem arrives later, and it arrives at the flex point.

What fails

A round CAT6 cable has four pairs of solid 23 AWG copper inside a rigid PVC or LSZH jacket. Solid copper is chosen for fixed installation because it punches down cleanly and has slightly lower resistance. It is not chosen for flexing: each bend cycle work-hardens the copper at the same point, and after some thousands of cycles the conductor cracks inside its insulation. The picture starts dropping when the lift moves, then stops altogether. A lift in a busy building makes several hundred trips a day, so "some thousands of cycles" is a matter of weeks or months.

Why flat cable is different

  • Stranded conductors: seven strands of 0.195 mm copper per conductor in CC-8251G-90, so each bend is shared across strands that can move relative to one another.
  • Flexible jacket: a soft FRLS PVC that bends to four times the cable thickness without cracking or kinking.
  • Flat profile: the cable bends across its thin axis only, hangs in one plane and does not twist around the lift's own travelling cable.
  • Individually sheathed pairs: each pair has its own flexible PVC sheath, which keeps the pair geometry — and therefore the CAT6 electrical values — stable while the cable moves.

What you give up

Stranded 24 AWG has higher DC resistance than solid 23 AWG (97.8 Ω/km max versus about 93.8 Ω/km), so PoE reach is a little shorter — hence the 60 m recommended run. In a lift that is never a limitation; the loop is short.

The comparison

PropertyRound CAT6 (solid)CAT6 Flat 4 Pair (CC-8251G-90)
ConductorSolid 23 AWGStranded 24 AWG, 7/0.195 mm
JacketRigid PVC / LSZHFlexible FRLS PVC
ProfileRound, ~6 mmFlat, 12 × 5 mm
Bend radius8× diameter, static4× thickness, continuous flexing
Flex lifeNot ratedBuilt for continuous travel
FireVariesIEC 60332-1, FRLS
Use in shaftFixed runs only (machine room to shaft top)The travelling loop

What to do

Use round CAT6 from the NVR to the shaft-top or mid-shaft junction box — it is fixed, and round cable is right for that. Use CAT6 Flat from the junction box to the car. Join the two in the box with a keystone or a coupler, never inside the moving loop.

QUESTIONS

Questions this guide answers

Can I use round CAT6 as a lift travelling cable?

It will work initially and fail at the flex point within months, because solid conductors crack under repeated bending. Use a flat stranded travelling cable for the moving section.

Is CAT6 flat cable the same as flat patch cable?

No. Flat patch cable is a thin desk cable with no flex rating and no FRLS jacket. A CAT6 flat lift cable is a travelling cable with stranded conductors and an FRLS jacket built for continuous movement.